Open vs closed cell
Industry ranges from the Spray Polyurethane Foam Alliance.
- Open cell
- Closed cell
R-value per inch
- Open cell:
R-3.6 to R-4.5
- Closed cell:
R-5.8 to R-6.9
- Open cell:
Density
- Open cell:
0.5 to 0.8 lb/ft³
- Closed cell:
1.8 to 2.3 lb/ft³
- Open cell:
Thickness that stops air
- Open cell:
About 3.5 to 5.5 in
- Closed cell:
About 1.5 in
- Open cell:
Foams side by side
Where each foam goes
Ratings for cold climates from the U.S. Department of Energy's Building America spray foam guide.
- Walls above ground: Either foam is preferred, and open cell works best at full wall depth.
- Rim joists and sill plates: Closed cell is preferred, and open cell is acceptable.
- Basements and crawl spaces: Closed cell is preferred, and open cell is not acceptable.
- Unvented attics and roof decks: Closed cell is preferred, and open cell is acceptable.
For what we carry for each job, see spray foam insulation.
The foams we carry
Green Valley's open cell is GVP 500 OC No Mix and its closed cell is GVP 2.0. The kit foam is Handi-Foam E84. See spray foam insulation and Handi-Foam kits.
- Green Valley open cell
- Handi-Foam kit
- Green Valley closed cell
Density
- Green Valley open cell:
0.50 lb/ft³
- Handi-Foam kit:
1.75 lb/ft³
- Green Valley closed cell:
2.0 lb/ft³
- Green Valley open cell:
R-value per inch
- Green Valley open cell:
R-3.9 per in
- Handi-Foam kit:
R-6.1 at 1 inR-11.7 at 2 in
- Green Valley closed cell:
R-7.2 per in
- Green Valley open cell:
Maker data sheets, with R-values measured after 180 days.
Moisture and air tests
- Moisture: GVP 500 OC, 7.54 perms at 3.5 in; Handi-Foam E84, 1.4 perms at 1.5 in; GVP 2.0, Class II at 1.1 in.
- Air: GVP 500 OC, under 0.02 L/s·m² at 3.5 in; Handi-Foam E84, 1 in or more; GVP 2.0, under 0.004 cfm/ft² at 1 in.
- Kit density: the 1.75 lb/ft³ is measured with the foam left to free rise.
What an attic needs
In cold zones, the code wants unvented attic foam to slow moisture, alone or under a coating or cover.
Closed cell does not always do that alone. Handi-Foam's kit foam needs the coating.
Code text and coatings
- Rule: IRC R806.5 (2021, 2024) in zones 5 to 8 requires air-impermeable attic foam to be Class II or have a Class II coating or covering.
- Covering: in direct contact with the foam's underside, and only over foams its report lists.
- Open cell sprayed air-impermeable falls under the same wording; ask your building department.
- No-Burn Plus ThB: not Class II (ER-305). FireShell F10E: Class III (ESR-3997).
- Class III means over 1.0 up to 10 perms; check the data sheet at your thickness.

Attic R-value minimums
The least foam R-value against the roof deck in an unvented attic.
- Zone 5B
R-20Front Range
- Zone 6B
R-25Eagle and Chaffee counties
- Zone 7
R-30Clear Creek, Summit, Grand, Park and Lake counties
From the 2021 and 2024 codes. The edition your town adopted, local changes and your permit date decide: Colorado Energy Office adoption map.
Table and energy code
- Source: Table R806.5, IRC 2021 and 2024.
- Counts toward the energy-code R-value, not instead of it; foam alone (item 5.1.1) follows the energy code.
- The data sheet and evaluation report set pass thickness and wait time.
Bare foam limits
Rim joists, sill plates and headers can skip the thermal barrier (the drywall or coating over foam) within these limits:
Thickness
3-1/4in or less
Handi-Foam kit thickness
2in or less
Kit foam
Density
0.5 to 2.0lb/ft³
Sprayed foam
Fire ratings
25 / 450or less
Flame spread / smoke
Everywhere else, cover the foam. See spray foam insulation.
Code sections
- Rim joist exception: IRC R316.5.11 (R303.5.11 in 2024).
- Kit cap: the 2 in limit for Handi-Foam E84 is in ESR-2717.
Frequently asked questions
Can I mix open cell and closed cell on one job?
Yes, in different places. Ask the foam maker before layering both in one wall.
How thick should spray foam be in an attic?
Enough inches to reach the attic minimum above, using the foam's R-value per inch. The code R-values still apply.
Can I spray foam in a Colorado winter?
Keep the chemical warm and the surface free of frost; ICP's temperatures are on Handi-Foam kits.
Reviewed by the Pop Supply team ·
Sources (16)
- ICP, Handi-Foam E84 data sheet TD062 (2025-10)
- Green Valley Products, GVP 500 OC NM sheet (2024-06-12)
- Green Valley Products, GVP 2.0 HFO data sheet (2025-05)
- ICC-ES, ESR-2717 evaluation report (2026-07)
- ICC-ES, ESR-3997 FireShell F10E report (2026-07)
- IAPMO UES, ER-305 No-Burn coatings (2026-07)
- SPFA, FAQs on open and closed cell
- DOE Building America, spray foam guide (2009-04)
- 2021 IRC, chapter 2 definitions (Colorado)
- 2021 IRC, R316 foam plastic (Colorado)
- 2021 IRC, R806.5 and Table R806.5 (Colorado)
- 2024 IRC, R303 foam plastic (Denver)
- 2024 IRC, R806.5 and Table R806.5 (Denver)
- 2021 IECC, climate zones by county (Colorado)
- PNNL, climate zones by county (PNNL-33270) (2022-09)
- Colorado Energy Office, building energy codes toolkit
Related pages: Spray foam · Handi-Foam kits · Board foot calculator · Code R-values · Crawl space guide · Delivery area